PART 2 — RESERVEDUpdated for the 2024 Ontario Building Code

2.2.1.6.Penetrations in Fire Separations and Fire-Rated Assemblies

(1) Penetrations of a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating shall conform to Articles 3.1.9.1. to 3.1.9.4.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.