Try BUILDAiD Beta
2.2.1.5.Fire Separations and Closures (See Note A-2.2.1.5.)
(1) Any wall, partition or floor assembly required to be a fire separation shall
(a) except as permitted by Sentence (2), be constructed as a continuous element, and
(b) as required in this Section, have a fire-resistance rating as specified. (See Note A-3.1.8.1.(1)(b))
(2) Openings in a fire separation shall be protected with closures, shafts or other means in conformance with Articles
3.1.8.3. to 3.1.8.19.
← Previous2.2.1.4. Separation of OccupanciesNext →2.2.1.6. Penetrations in Fire Separations and Fire-Rated
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.