Section 9.4 — Structural Requirements
Full text of Section 9.4 (Structural Requirements) — Division B, Part 9 (Housing and Small Buildings) of the 2024 Ontario Building Code, with every article reproduced below.
9.4.1.Structural Design Requirements and Application Limitations
9.4.1.1.General (See Note A-9.4.1.1.) permalink →
(1) Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall
(a) conform to requirements provided elsewhere in this Part,
(b) be designed according to good engineering practice such as provided in the CWC 2014, “Engineering Guide for
Wood Frame Construction,” or
(c) be designed according to Part 4 using the loads and deflection and vibration limits specified in,
(i) this Part, or
(ii) Part 4.
(2) Where floor framing is designed in accordance with Clause (1)(b) or (c) and where supporting wall framing and
fastenings, or footings, are designed according to Clause (1)(a), the maximum specified live load on the floor according to
Table 4.1.5.3. shall not exceed 2.4 kPa.
(3) Location-specific information for structural design, including snow and wind loads and seismic spectral response
accelerations, shall be determined according to MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(See Note A-9.4.1.1.(3))
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.4.2.Specified Loads
9.4.2.1.Application (See Note A-9.4.2.1. and 9.4.2.2.) permalink →
(1) This Subsection applies to light-frame construction whose wall, floor and roof planes are generally comprised of
frames of small repetitive structural members, and where
(a) the roof and wall planes are clad, sheathed or braced on at least one side,
(b) the small repetitive structural members are spaced not more than 600 mm o.c.,
(c) the clear span of any structural member does not exceed 12.2 m,
(d) the maximum deflection of the structural roof members conforms to Article 9.4.3.1.,
(e) the maximum total roof area, notwithstanding any separation of adjoining buildings by firewalls, is 4 550 m2, and
(f) for flat roofs, there are no significant obstructions on the roof, such as parapet walls, spaced closer than the distance
calculated by
Do = 10(Ho – 0.8 Ss / γ)
where
Do = minimum distance between obstructions, m,
Ho = height of the obstruction above the roof, m,
Ss = ground snow load, kPa, and
γ = specific weight of snow taken as 4.0 kN/m3 or 0.43Ss + 2.2 kN/m3, whichever is lesser.
9.4.2.2.Specified Snow Loads (See Note A-9.4.2.1. and 9.4.2.2.) permalink →
(1) Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the
following formula:
S = CbSs + Sr
where
S = specified snow load,
Cb = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and
0.55 for all other roofs,
Ss = 1-in-50 year ground snow load in kPa, determined according to MMAH Supplementary Standard SB-1,
“Climatic and Seismic Data,” and
Sr = associated 1-in-50 year rain load in kPa, determined according to MMAH Supplementary Standard
SB-1, “Climatic and Seismic Data.”
(2) In no case shall the specified snow load be less than 1 kPa.
(3) Bow string, arch or semi-circular roof trusses having an unsupported span greater than 6 m shall be designed in
conformance with the snow load requirements in Subsection 4.1.6.
(4) Where the height of a roof step at the intersection of an upper level roof and a lower level roof is greater than 2 m,
and the upper level roof has a slope less than 1 in 6 and an area greater than 600 m 2, the specified snow load on the lower
level roof shall be
(a) for distances from the roof step that are less than or equal to the drift length, x d, calculated in accordance with
Sentence (5), not less than 1.5 times the specified snow load, S, calculated using the formula in Sentence (1) with Cb
equal to 0.55, and
(b) for distances from the roof step that are greater than the drift length, x d, calculated in accordance with Sentence (5),
as specified in Sentence (1).
(5) For the purposes of Sentence (4), the drift length, xd, in m, shall be calculated as follows:
where
h = height of the roof step, in m, and
γ = specific weight of snow as specified in Clause 9.4.2.1.(1)(f).
9.4.2.3.Platforms Subject to Snow and Occupancy Loads permalink →
(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall
be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated
area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1))
9.4.2.4.Attics and Roof Spaces permalink →
(1) Ceiling joists or truss bottom chords in residential attic or roof spaces having limited accessibility that precludes the
storage of equipment or material shall be designed for a total specified load of not less than 0.35 kPa, where the total
specified load is the sum of the specified dead load plus the specified live load of the ceiling. (See Note A-9.4.2.4.(1))
9.4.3.Deflections
(1) The maximum deflection of structural members shall conform to Table 9.4.3.1.
(2) Dead loads need not be considered in computing deflections referred to in Sentence (1).
Table 9.4.3.1.
Maximum Deflections
Forming Part of Sentence 9.4.3.1.(1)
Max. Allowable Deflection as an
Structural Members Type of Ceiling Supported
Expressed Ratio of the Clear Span
No ceiling 1/180
Roof rafters, roof joists and roof beams Other than plaster or gypsum board 1/240
Plaster or gypsum board 1/360
Other than plaster or gypsum board 1/240
Ceiling joists
Plaster or gypsum board 1/360
Floor beams, floor joists and floor decking All cases 1/360
Beams, joists and decking for balconies, decks and Serving a single dwelling unit 1/240
other accessible exterior platforms Other 1/360
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.4.4.Foundation Conditions
9.4.4.1.Allowable Bearing Pressures permalink →
(1) Footing sizes for shallow foundations shall be
(a) determined in accordance with Section 9.15., or
(b) designed in accordance with Section 4.2. using,
(i) the maximum allowable bearing pressures in Table 9.4.4.1., or
(ii) allowable bearing pressures determined from subsurface investigation.
(2) The design procedures described in Section 4.2. are permitted to be used in lieu of the design procedures in this
Subsection.
Table 9.4.4.1.
Allowable Bearing Pressure for Soil or Rock
Forming Part of Sentence 9.4.4.1.(1)
Type and Condition of Soil or Rock Maximum Allowable Bearing Pressure, kPa
Dense or compact sand or gravel(1) 150
Loose sand or gravel(1) 50
Dense or compact silt(1) 100
Stiff clay(1) 150
Firm clay(1) 75
Soft clay(1) 40
Till 200
Clay shale 300
Sound rock 500
Notes to Table 9.4.4.1.:
(1) See Note A-Table 9.4.1.1.
(3) The design procedures described in Section 4.2. shall be used where,
(a) deep foundations are used,
(b) the footing size falls outside the scope of this Section, or
(c) the foundation is constructed on peat, filled ground or on sensitive clays as described in Article 9.15.1.1.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
9.4.4.2.Foundation Capacity in Weaker Soil and Rock permalink →
(1) Where a soil or rock within a distance equal to twice the footing width below the bearing surface has a lower
allowable bearing pressure than that at the bearing surface as shown in Article 9.4.4.1., the design capacity of the
foundation shall not be greater than would cause the weakest soil or rock to be stressed beyond its allowable bearing
pressure.
(2) In calculating subsurface pressures referred to in Sentence (1), the loads from the footings shall be assumed to be
distributed uniformly over a horizontal plane within a frustum extending downward from the footing at an angle of 60° to
the horizontal.
9.4.4.3.High Water Table permalink →
(1) Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface
equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.
(1) Where a foundation is located in an area where soil movement caused by changes in soil moisture content, freezing,
or chemical-microbiological oxidation is known to occur to the extent that it will damage a building, measures shall be
taken to preclude such movement or to reduce the effects on the building so that the building’s stability and the
performance of assemblies will not be adversely affected. (See Note A-9.4.4.4.(1))
9.4.4.5.Reserved
9.4.4.6.Walls Supporting Drained Earth (See Note A-9.4.4.6. and 9.15.1.1.)) permalink →
(1) Except where constructed in accordance with Section 9.15., walls supporting drained earth shall be designed
(a) for a pressure equivalent to that exerted by a fluid with a density of not less than 480 kg/m 3 and a depth equal to that
of the retained earth, or
(b) in accordance with Section 4.2. so as to be able to resist the loads and effects described in Article 4.1.2.1.
(2) Walls supporting other than drained earth shall be designed
(a) for the pressure described in Clause (1)(a) plus the fluid pressure of the surcharge, or
(b) in accordance with Section 4.2. so as to be able to resist the loads and effects described in Article 4.1.2.1.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.