Section 6.8 — Equipment Access
Full text of Section 6.8 (Equipment Access) — Division B, Part 6 (Heating, Ventilating and Air-Conditioning) of the 2024 Ontario Building Code, with every article reproduced below.
6.8.1.Openings
6.8.1.1.Access Openings permalink →
(1) Any covering of an access opening through which a person could enter shall be openable from the inside without the
use of keys where there is a possibility of the opening being accidentally closed while the system or equipment is being
serviced.
6.8.1.2.Openings in Air Duct Systems permalink →
(1) Air duct systems shall have no openings other than those required for the proper operation and maintenance of the
system.
(2) Access openings shall be provided in duct systems to allow the removal of material that may accumulate in plenums
and ducts.
6.8.1.3.Odour Removal Equipment permalink →
(1) When odour removal equipment of the adsorption type is used, it shall be
(a) installed to allow access so that adsorption material can be reactivated or renewed, and
(b) protected from dust accumulation by air filters installed on the inlet side.
(2) Facilities for flushing and drainage shall be provided where filters are designed to be washed in place.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.