OBC DIVISION B · PART 5 — ENVIRONMENTAL SEPARATIONUpdated for the 2024 Ontario Building Code

Section 5.6 — Precipitation

Full text of Section 5.6 (Precipitation) — Division B, Part 5 (Environmental Separation) of the 2024 Ontario Building Code, with every article reproduced below.

5.6.1.Protection from Precipitation

5.6.1.1.Required Protection from Precipitation (See Note A-5.6.1.1.) permalink →

(1) Except as provided in Sentence (2), where a building component or assembly is exposed to precipitation, the component or assembly shall (a) minimize ingress of precipitation into the component or assembly, and (b) prevent ingress of precipitation into interior space. (2) Protection from ingress of precipitation is not required where it can be shown that such ingress will not adversely affect any of (a) the health or safety of building users, (b) the intended use of the building, or (c) the operation of building services.

5.6.1.2.Installation of Protective Materials permalink →

(1) Where protective materials are applied to assemblies to provide the required protection from precipitation, they shall be installed so as to shed precipitation or otherwise minimize its entry into the assembly and prevent its penetration through the assembly. (See Note A-5.6.1.2.(1)) (See also Clause 5.3.1.2.(1)(d)) (2) Where protective materials described in Sentence (1) are part of a vegetative roofing system, they shall be resistant to root and rhizome penetration when tested in accordance with ANSI/GRHC/SPRI VR-1, “Procedure for Investigating Resistance to Root or Rhizome Penetration on Vegetative Roofs.” (See Note A-5.6.1.2.(2))

5.6.2.Sealing, Drainage, Accumulation and Disposal

5.6.2.1.Sealing and Drainage (See Note A-5.6.2.1.) permalink →

(1) Except as provided in Sentence (2), materials, components, assemblies, joints in materials, junctions between components and junctions between assemblies exposed to precipitation shall be (a) sealed to prevent ingress of precipitation, or (b) drained to direct precipitation to the exterior. (2) Sealing or drainage are not required where it can be shown that the omission of sealing and drainage will not adversely affect any of, (a) the health or safety of building users, (b) the intended use of the building, or (c) the operation of building services.

5.6.2.2.Accumulation and Disposal permalink →

(1) Where water, snow or ice can accumulate on a building, provision shall be made to minimize the likelihood of hazardous conditions arising from such accumulation. (2) Where precipitation can accumulate on sloped or horizontal assemblies, provision shall be made for drainage conforming with Section 7.4. (3) Where downspouts are provided and are not connected to a sewer, provisions shall be made to, (a) divert the water from the building, and (b) prevent soil erosion. (4) Junctions between vertical assemblies, and sloped or horizontal assemblies, shall be designed and constructed to minimize the flow of water from the sloped or horizontal assembly onto the vertical assembly.

5.6.2.3.Solar Collector Systems permalink →

(1) A solar collector system is permitted to be installed above roofing materials conforming to Table 5.9.1.1.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand any provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.