5.6.1.2.Installation of Protective Materials
(1) Where protective materials are applied to assemblies to provide the required protection from precipitation, they shall
be installed so as to shed precipitation or otherwise minimize its entry into the assembly and prevent its penetration
through the assembly. (See Note A-5.6.1.2.(1)) (See also Clause 5.3.1.2.(1)(d))
(2) Where protective materials described in Sentence (1) are part of a vegetative roofing system, they shall be resistant
to root and rhizome penetration when tested in accordance with ANSI/GRHC/SPRI VR-1, “Procedure for Investigating
Resistance to Root or Rhizome Penetration on Vegetative Roofs.” (See Note A-5.6.1.2.(2))
← Previous5.6.1.1. Required Protection from Precipitation (See NoteNext →5.6.2.1. Sealing and Drainage (See Note A-5.6.2.1.)
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.