PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code

9.9.6.5.Direction of Door Swing

(1) Except as permitted by Sentence (1.1) and except for doors serving single dwelling unit or a house with a secondary suite, exit doors that are required to swing shall swing in the direction of exit travel. (1.1) An exit door need not swing in the direction of exit travel where it serves (a) a room, suite or floor area having an occupant load of not more than 60 persons, or (b) as part of a means of egress from more than one floor area and the floor areas so served have a total occupant load of not more than 60 persons.. (2) Doors that open onto a corridor or other facility that provides access to exit from a room or suite having an occupant load of more than 60 persons shall swing on the vertical axis in the direction of exit travel. (3) Doors that divide a corridor that is not wholly contained within a suite shall swing in the direction of exit travel. (4) Where a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall (a) swing in opposite directions, with the door on the right hand-side swinging in the direction of exit travel, or (b) swing in both directions.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.