9.9.4.6.Openings Near Exit Doors
(1) This Article applies to
(a) exit doors serving other than an individual dwelling unit, and
(b) exit doors serving an individual dwelling unit where there is no second and separate exit from the dwelling unit.
(2) Where an exterior exit door described in Sentence (1) in one fire compartment is within 3 m horizontally of an
unprotected opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior
angle of less than 135°, the opening shall be protected with wired glass in fixed steel frames or glass block conforming to
Articles 9.10.13.5. and 9.10.13.7. or with a rated closure conforming to Table 9.10.13.1. with respect to the rating of the
fire separation between the two compartments.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.9.4.5. Openings in Exterior Walls of ExitsNext →9.9.4.7. Stairways in Group D or E Buildings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.