9.33.6.12.Return-Air Inlets
(1) Return-air inlets shall not be installed in an enclosed room or crawl space that provides combustion air to a furnace.
(2) Except for floor levels which are less than 900 mm above or below an adjacent floor level which is provided with a
return-air inlet, at least one return-air inlet shall be provided in each floor level in a dwelling unit.
(3) Provision shall be made for the return of air from all rooms by leaving gaps beneath doors, using louvred doors or
installing return duct inlets.
← Previous9.33.6.11. Warm-Air Supply OutletsNext →9.33.6.13. Return-Air System (See Note A-9.33.6.13.)
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.