9.33.6.10A.Supply, Return, Intake and Exhaust Openings
(1) Supply, return and exhaust air openings in rooms or spaces shall be protected by grilles having openings of a size
that will not allow the passage of a 15 mm diameter sphere.
(2) Outdoor air intakes and exhaust outlets at the building exterior shall be designed or located so that the air entering
the building system will not contain more contaminants than the normal exterior air.
(3) Exterior openings for outdoor air intakes and exhaust outlets shall be shielded from the entry of snow and rain and
shall be fitted with corrosion-resistant screens of mesh having openings not larger than 15 mm, except where climatic
conditions may require larger openings.
(4) Screens required in Sentence (3) shall be accessible for maintenance.
← Previous9.33.6.10. Warm-Air Supply Outlets and Return Inlets — GeneNext →9.33.6.11. Warm-Air Supply Outlets
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.