9.27.3.3.Required Sheathing Membrane and Installation
(1) Except as provided in Articles 9.27.3.4. to 9.27.3.6., at least one layer of sheathing membrane shall be applied
beneath siding, stucco or masonry veneer.
(2) Sheathing membrane required in Sentence (1) shall be applied so that joints are lapped not less than 100 mm.
(3) Where sheathing membrane required in Sentence (1) is applied horizontally, the upper sheets shall overlap the lower
sheets.
← Previous9.27.3.2. Sheathing Membrane Material StandardNext →9.27.3.4. Insulating Sheathing in Lieu of Sheathing Membra
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.