PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.27.3.1.Elements of the Second Plane of Protection (See Note A-9.27.3.1.)
(1) The second plane of protection shall consist of a drainage plane having an appropriate inner boundary and flashing
to dissipate rainwater to the exterior.
(2) Except for cladding systems conforming to Subsection 9.27.14., the inner boundary of the drainage plane shall
comply with Articles 9.27.3.2. to 9.27.3.6.
(3) The protection provided by the second plane of protection shall be maintained
(a) at wall penetrations created by the installation of components and services such as windows, doors, ventilation
ducts, piping, wiring and electrical outlets, and
(b) at the interface with other wall assemblies.
(4) Flashing material and its installation shall comply with Articles 9.27.3.7. and 9.27.3.8.
← Previous9.27.2.4. Protection of Cladding from MoistureNext →9.27.3.2. Sheathing Membrane Material Standard
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.