9.27.2.4.Protection of Cladding from Moisture
(1) A clearance of not less than 200 mm shall be provided between finished ground and cladding that is adversely
affected by moisture, such as untreated wood, plywood, OSB, waferboard and hardboard.
(2) A clearance of not less than 50 mm shall be provided between a roof surface and cladding that is adversely affected
by moisture, such as untreated wood, plywood, OSB, waferboard and hardboard.
← Previous9.27.2.3. First and Second Planes of ProtectionNext →9.27.3.1. Elements of the Second Plane of Protection (See
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.