PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.25.5.1.General (See Note A-9.25.5.1.)
(1) Except as provided in Sentences (2) to (4), sheet and panel-type materials incorporated into assemblies described in
Article 9.25.1.1. shall conform to Article 9.25.5.2. where
(a) the material has
(i) an air leakage characteristic less than 0.1 L/(s×m2) at 75 Pa, and
(ii) a water vapour permeance less than 60 ng/(Pa×s×m 2) when measured in accordance with ASTM E96 / E96M,
“Standard Test Methods for Water Vapor Transmission of Materials,” using the desiccant method (dry cup),
and (See Note A-9.25.5.1.(1)(a)(ii))
(b) the intended use of the interior space where the materials are installed will not result in high moisture generation.
(See Note A-9.25.5.1.(1))
(2) Where the intended use of the interior space will result in high moisture generation, the assembly shall be designed
according to Part 5.
(3) Wood-based sheathing materials not more than 12.5 mm thick and complying with Article 9.23.17.2. need not
comply with Sentence (1). (See Note A-9.25.5.1.(3))
(4) Where a material has a water vapour permeance not less than 30 ng/(Pa×s×m2) and a thermal resistance not less
than 0.7 (m2×K)/W and the heating degree-days of the building location are less than 6000, the assembly need not comply
with Sentence (1).
← Previous9.25.4.3. Installation of Vapour BarriersNext →9.25.5.2. Position of Low Permeance Materials (See Note A-
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.