9.25.3.2.Air Barrier System Properties (See Note A-9.25.5.1.(1))
(1) Sheet and panel type materials intended to provide the principal resistance to air leakage shall have an air leakage
characteristic not greater than 0.02 L/(s∙m 2) measured at an air pressure differential of 75 Pa.
(2) Where polyethylene sheet is used to provide the airtightness in the air barrier system, it shall conform to
CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet for Use in Building Construction.”
← Previous9.25.3.1. Required Barrier to Air LeakageNext →9.25.3.3. Continuity of the Air Barrier System
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.