PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.23.12.2.Openings in Loadbearing Walls
(1) Openings in loadbearing walls greater than the required stud spacing shall be framed with lintels designed to carry
the superimposed loads to adjacent studs. (See Note A-9.23.10.6.(3))
(2) Except as provided in Sentence 9.23.12.3.(2), where 2 or more members are used in lintels, they shall be fastened
together with not less than 82 mm nails in a double row, with nails not more than 450 mm apart in each row.
(3) Lintel members are permitted to be separated by filler pieces.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.