PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.23.12.1.Openings in Non-Loadbearing Walls
(1) Except as provided in Sentence (2), openings in non-loadbearing walls shall be framed with not less than 38 mm
material the same width as the studs, securely nailed to adjacent studs.
(2) Openings for doors in non-loadbearing walls required to be fire separations with a fire-resistance rating shall be
framed with the equivalent of at least two 38 mm thick members that are the same width as the wall plates.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.