9.22.9.3.Clearance to Combustible Framing

(1) Not less than a 100 mm clearance shall be provided between the back and sides of a fireplace and combustible framing, except that a 50 mm clearance is permitted where the fireplace is located in an exterior wall. (2) Not less than a 50 mm clearance shall be provided between the back and sides of the smoke chamber of a fireplace and combustible framing, except that a 25 mm clearance is permitted where the fireplace is located in an exterior wall.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.