9.22.2.2.Firebrick Liners
(1) Fireplace liners shall be not less than
(a) 50 mm thick for the sides and back, and
(b) 25 mm thick for the floor.
(2) Firebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB-10.3, “Air Setting
Refractory Mortar.”
(3) Joints between a firebrick liner and the adjacent backing masonry shall be offset.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.