PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.9.5.Interconnected Floor Spaces
(1) Except as permitted in Article 9.9.4.7., interconnected floor spaces shall conform to the requirements of
Subsection 3.2.8.
← Previous9.10.9.4. Floor AssembliesNext →9.10.9.6. General Requirements for Penetrations of Fire Se
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.