9.10.9.20.Exhaust Ducts Serving More Than One Fire Compartment
(1) Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall
have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure.
(2) Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust directly into the duct in the
vertical service space.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.