PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code

9.10.9.19.Separation of Repair Garages

(1) Except as provided in Sentences (2) and (3), a repair garage shall be separated from other occupancies by a fire separation having a fire-resistance rating of not less than 2 h. (2) Ancillary spaces directly serving a repair garage, including waiting rooms, reception rooms, tool and parts storage areas and supervisory office space, need not be separated from the repair garage but shall be separated from other occupancies as required in Sentence (1). (3) The fire separation referred to in Sentence (1) shall have a fire-resistance rating of not less than 1 h, where (a) the building is not more than one storey in building height, (b) the building is operated as a single suite, and (c) the only occupancy other than the repair garage is a mercantile occupancy. (4) Except as provided in Sentence (5), where a building containing a repair garage also contains a dwelling unit, an air barrier system conforming to Subsection 9.25.3. shall be installed between the dwelling unit and the suite containing the garage to provide an effective barrier to gas and exhaust fumes. (See Note A-9.10.9.18.(4)) (5) Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.