PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.9.13.Separation of Residential Occupancies
(1) Except as provided in Sentences (2) and (4), residential occupancies shall be separated from all other major
occupancies by a fire separation having a fire-resistance rating of not less than 1 h.
(2) Except as provided in Sentence (3), a major occupancy classified as a residential occupancy, including live/work
units, shall be separated from other major occupancies classified as mercantile or medium hazard industrial occupancies
by a fire separation having a fire-resistance rating of not less than 2 h.
(3) Where not more than two dwelling units or live/work units are located in a building containing a mercantile
occupancy, such mercantile occupancy shall be separated from the dwelling units or live/work units by a fire separation
having not less than 1 h fire-resistance rating.
(4) The requirement for fire separations between major occupancies in Sentence (1) is waived for the occupancies
allowed within live/work units.
← Previous9.10.9.12. Concealed Spaces Above Fire SeparationsNext →9.10.9.14. Residential Suites in Industrial Buildings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.