9.10.9.12.Concealed Spaces Above Fire Separations
(1) Except as provided in Sentence (2), a horizontal service space or other concealed space located above a required
vertical fire separation shall be divided at the fire separation by an equivalent fire separation within the space.
(2) Where a horizontal service space or other concealed space is located above a required vertical fire separation other
than a vertical shaft, such space need not be divided as required in Sentence (1) provided the construction between such
space and the space below is constructed as a fire separation having a fire-resistance rating not less than that required for
the vertical fire separation, except that where the vertical fire separation is not required to have a fire-resistance rating
greater than 45 min, the fire-resistance rating of the ceiling is permitted to be reduced to 30 min.
← Previous9.10.9.11. Reduction in Thickness of Fire Separation by BeaNext →9.10.9.13. Separation of Residential Occupancies
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.