PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.14.5.Construction of Exposing Building Face and Walls Above Exposing
Building Face
(1) Except as provided in Sentences (4) to (14), each exposing building face and any exterior wall located above an
exposing building face that encloses an attic or roof space shall be constructed in conformance with Table 9.10.14.5. and
Subsection 9.10.8. (See Note A-9.10.14.5.(1))
(2) Cladding on exposing building faces and exterior walls located above exposing building faces need not conform to
the type of cladding required by Table 9.10.14.5. where
(a) the exposing building face is constructed with no unprotected openings,
(b) the limiting distance is not less than 0.6 m, and
(c) the cladding
(i) conforms to Subsection 9.27.12.,
(ii) is installed without furring members over not less than 12.7 mm thick gypsum sheathing or over masonry,
(iii) has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1.(2), and
(iv) is not more than 2 mm in thickness exclusive of fasteners, joints and local reinforcements.
Table 9.10.14.5.
Minimum Construction Requirements for Exposing Building Faces
Forming Part of Sentence 9.10.14.5.(1)
Maximum Area of Unprotected
Occupancy Classification Minimum Required Fire- Type of Construction Type of Cladding
Openings Permitted, % of
of Building Resistance Rating Required Required
Exposing Building Face Area
0 - 10 1h Noncombustible Noncombustible
Residential, business and Combustible or
>10 but ≤25 1h Noncombustible
personal services, and noncombustible
low-hazard industrial
Combustible or Combustible or
>25 but <100 45 min
noncombustible noncombustible
0 - 10 2h Noncombustible Noncombustible
Combustible or
Mercantile and medium- >10 but ≤25 2h Noncombustible
noncombustible
hazard industrial
Combustible or Combustible or
>25 but <100 1h
noncombustible noncombustible
(3) Reserved.
(4) Except as provided in Sentence (5), where a garage or accessory building serves one dwelling unit only and is
detached from any building, the exposing building face
(a) need not conform to the minimum required fire-resistance rating stated in Table 9.10.14.5., where the limiting
distance is 0.6 m or more,
(b) shall have a fire-resistance rating of not less than 45 min where the limiting distance is less than 0.6 m, and
(c) need not conform to the type of cladding and type of construction required by Table 9.10.14.5., regardless of the
limiting distance.
(5) The requirements regarding fire-resistance rating, type of construction and type of cladding need not apply to the
exposing building face of a detached garage or accessory building facing a dwelling unit, where
(a) the detached garage or accessory building serves only one dwelling unit,
(b) the detached garage or accessory building is located on the same property as that dwelling unit, and
(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
(6) Except for buildings containing one or two dwelling units only, combustible projections on the exterior of a wall that
are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted
within
(a) 1.2 m of a property line or the centre line of a public way, or
(b) 2.4 m of a combustible projection on another building on the same property.
(7) Reserved.
(8) Reserved.
(9) Reserved.
(10) Reserved.
(11) Reserved.
(12) Where roof soffits project to less than 1.2 m from the property line, the centre line of a public way, or an imaginary
line between two buildings or fire compartments on the same property, they shall
(a) have no openings, and
(b) be protected by
(i) not less than 0.38 mm thick sheet steel,
(ii) unvented aluminum conforming to CAN/CGSB-93.2-M, “Prefinished Aluminum Siding, Soffits, and Fascia,
for Residential Use,”
(iii) not less than 12.7 mm thick gypsum soffit board or gypsum ceiling board installed according to CSA A82.31-
M, “Gypsum Board Application,”
(iv) not less than 11 mm thick plywood,
(v) not less than 12.5 mm thick OSB or waferboard, or
(vi) not less than 11 mm thick lumber.
(See Note A-3.2.3.6.(2))
(13) Heavy timber and steel columns need not conform to the requirements of Sentence (1) provided the limiting distance
is not less than 3 m.
(14) Non-loadbearing wall components need not have a minimum fire-resistance rating, where the building
(a) is 1 storey in building height,
(b) is of noncombustible construction,
(c) is classified as low-hazard industrial occupancy and is used only for low fire load occupancies such as power
generating plants or plants for the manufacture or storage of noncombustible materials, and
(d) has a limiting distance of 3 m or more.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.10.14.4. Openings in Exposing Building FaceNext →9.10.14.6. Minor Openings in Exposing Building Face
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.