PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.12.3.Exterior Walls Meeting at an Angle
(1) Except as provided in Article 9.9.4.5., where exterior walls of a building meet at an external angle of 135° or less,
the horizontal distance from an unprotected opening in one exterior wall to an unprotected opening in the other exterior
wall shall be not less than 1.2 m, where these openings are
(a) in different fire compartments, or
(b) in different dwelling units, ancillary spaces or common spaces in a house with a secondary suite.
(2) Except as provided in Sentence (3), the exterior wall of each fire compartment referred to in Sentence (1) within the
1.2 m distance shall have a fire-resistance rating not less than that required for the interior vertical fire separation
between the compartment and the remainder of the building.
(3) Where interior walls between dwelling units, ancillary spaces or common spaces in a house with a secondary suite
are not constructed as fire separations, the exterior wall of each dwelling unit, ancillary space or common space referred
to in Sentence (1) within the 1.2 m distance shall be finished on the interior with not less than 15.9 mm thick Type X
gypsum board.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.