PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.12.2.Location of Skylights
(1) Where a wall in a building is exposed to a fire hazard from an adjoining roof of a separate fire compartment that is
not sprinklered in the same building, the roof shall contain no skylights within a horizontal distance of 5 m of the
windows in the exposed wall.
← Previous9.10.12.1. Termination of Floors or MezzaninesNext →9.10.12.3. Exterior Walls Meeting at an Angle
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.