PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
7.6.2.6.Premise Isolation (See Note A-7.6.2.6.)
(1) Buildings or facilities where a moderate hazard or severe hazard may be caused by backflow shall be provided with
premise isolation of the potable water system by the installation of a backflow preventer selected in accordance with
Clauses 5.3.4.2.(b) and (c) of CSA B64.10, “Selection and installation of backflow preventers.”
(2) Buildings of residential occupancy within the scope of Part 9 are not required to be isolated unless they have access
to an auxiliary water supply.
(3) Except as provided in Sentence (1), where no direct connection exists between the auxiliary water supply and the
potable water system, premise isolation shall be provided by a dual check valve backflow preventer conforming to
CSA B64.6, “Dual check valve (DuC) backflow preventers.”
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.