7.6.2.4.Backflow from Fire Protection Systems
(1) A backflow preventer shall not be required in residential full flow-through fire sprinkler/standpipe systems in which
the pipes and fittings are constructed of potable water system materials.
(2) Except as required by Sentence (4), potable water system connections to fire sprinkler and standpipe systems shall
be protected against backflow caused by back-siphonage or back pressure in conformance with Clauses (a) to (g), as
applicable:
(a) residential partial flow-through fire sprinkler/standpipe systems in which the pipes and fittings are constructed of
potable water system materials shall be protected by a dual check valve backflow preventer conforming to
(i) CSA B64.6, “Dual check valve (DuC) backflow preventers,” or
(ii) CSA B64.6.1, “Dual check valve backflow preventers for fire protection systems (DuCF),”
(b) provided that the systems do not use antifreeze or other additives of any kind and that all pipes and fittings are
constructed of potable water system materials, Class 1 fire sprinkler/standpipe systems shall be protected by a single
or dual check valve backflow preventer conforming to
(i) CSA B64.6, “Dual check valve (DuC) backflow preventers,” or
(ii) CSA B64.9, “Single check valve backflow preventers for fire protection systems (SCVAF),”
(c) provided that the systems do not use antifreeze or other additives of any kind, Class 1 fire sprinkler/standpipe
systems not covered by Clause (b) as well as Class 2 and Class 3 fire sprinkler/standpipe systems shall be protected
by a double check valve backflow preventer conforming to
(i) CSA B64.5, “Double check valve (DCVA) backflow preventers,” or
(ii) CSA B64.5.1, “Double check valve backflow preventers for fire protection systems (DCVAF),”
(d) Class 1, Class 2 or Class 3 Class 3 fire sprinkler/standpipe systems in which antifreeze or other additives are used
shall be protected by a reduced pressure principle backflow preventer conforming to
(i) CSA B64.4, “Reduced pressure principle (RP) backflow preventers,” or
(ii) CSA B64.4.1, “Reduced pressure principle backflow preventers for fire protection systems (RPF),”
installed on the portion of the system that uses the additives and the balance of the system shall be protected as
required by Clause (b) or (c),
(e) Class 4 and Class 5 fire sprinkler/standpipe systems shall be protected by a reduced pressure principle backflow
preventer conforming to
(i) CSA B64.4, “Reduced pressure principle (RP) backflow preventers,” or
(ii) CSA B64.4.1, “Reduced pressure principle backflow preventers for fire protection systems (RPF),”
(f) Class 6 fire sprinkler/standpipe systems shall be protected by a double check valve backflow preventer conforming
to
(i) CSA B64.5, “Double check valve (DCVA) backflow preventers,” or
(ii) CSA B64.5.1, “Double check valve backflow preventers for fire protection systems (DCVAF).”
(g) where a potentially severe health hazard may be caused by backflow, Class 6 fire sprinkler/standpipe systems shall
be protected by a reduced pressure principle backflow preventer conforming to
(i) CSA B64.4, “Reduced pressure principle (RP) backflow preventers,” or
(ii) CSA B64.4.1, “Reduced pressure principle backflow preventers for fire protection systems (RPF).”
(3) Backflow preventers required by Sentence (2) shall be installed upstream of the fire department pumper connection.
(4) Where a reduced pressure principle backflow preventer is required on a water service pipe at a fire service
connection located on the same premises as the fire service pipe in Class 3, 4, 5 and 6 fire sprinkler/standpipe systems, a
reduced pressure principle backflow preventer conforming to CSA B64.4.1, “Reduced pressure principle backflow
preventers for fire protection systems (RPF),” shall also be required on the fire service connection.
← Previous7.6.2.3. Backflow Caused by Back PressureNext →7.6.2.5A. Backflow from Buildings with a Solar Domestic Ho
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.