PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.4.10.10.Hydraulic Loads to Roof Gutters

(1) The hydraulic load that is drained to a roof gutter shall conform to Table 7.4.10.10. Table 7.4.10.10. Maximum Permitted Hydraulic Load Drained to a Roof Gutter Forming Part of Article 7.4.10.10. Maximum Hydraulic Load, L Nominal Pipe Size of Gutter, Area of Gutter,cm3 Slope NPS 1 in 200 1 in 100 1 in 50 1 in 25 3 22.8 406 559 812 1 140 4 40.5 838 1 190 1 700 2 410 5 63.3 1 470 2 080 2 950 4 170 6 91.2 2 260 3 200 4 520 6 530 7 124.1 3 250 4 600 6 500 9 190 8 162.1 4 700 6 600 9 400 13 200 10 253.4 8 480 12 000 17 000 23 600

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.