PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.2.3.1.Traps

(1) Except as provided for in Sentence (2), traps shall (a) have a trap seal depth of not less than 38 mm, (b) be so designed that failure of the seal walls will cause exterior leakage, and (c) have a water seal that does not depend on the action of moving parts. (See Note A-7.2.3.1.(1) and (3)) (2) The trap seal depth on fixtures draining to an acid waste system shall be a minimum of 50 mm. (3) Except for a floor-mounted service sink, every trap that serves a lavatory, a sink or a laundry tray shall (a) be provided with a cleanout plug located at the lowest point of the trap and of the same material as the trap, except that a cast iron trap shall be provided with a brass cleanout plug, or (b) be designed so that part of the trap can be removed for cleaning purposes. (See Note A-7.2.3.1.(1) and (3)) (4) A bell trap shall not be installed in a drainage system. (5) A drum trap shall not be installed in a drainage system. (6) Except as permitted in Sentence (7), no bottle trap shall be used in a plumbing system. (7) A bottle trap may be used on a laboratory sink or other fixture equipped with corrosion resistant fittings. (8) No running trap shall be installed in a plumbing system unless an accessible handhole is provided for cleaning of the trap, and where the trap is too small to accommodate a handhole, a cleanout shall be provided.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.