PART 4 — STRUCTURAL DESIGNUpdated for the 2024 Ontario Building Code

4.1.5.4.Loads for Occupancy Served

(1) The following shall be designed to carry not less than the specified load required for the occupancy they serve, provided they cannot be used by an assembly of people as a viewing area: (a) corridors, lobbies and aisles not more than 1 200 mm wide, (b) all corridors above the first storey of residential areas of apartments, hotels and motels, and (c) interior balconies and mezzanines.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.