PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.6.5.2.Vibration Isolation Connectors

(1) Except as permitted by Sentence (2), vibration isolation connectors in air duct systems shall be noncombustible. (2) Combustible fabric vibration isolation connectors are permitted provided they (a) are not more than 250 mm long, (b) comply with the flame-resistance requirements of CAN/ULC-S109, “Standard Method for Flame Tests of Flame- Resistant Fabrics and Films,” and (c) are not used in a location where they are exposed to heated air or radiation from heat sources that could cause the exposed surface temperature to be more than 120°C.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.