3.6.2.9.Storage of Oxygen Containers
(1) In a Group B, Division 2 or 3 occupancy or in a retirement home, a room for the storage of oxygen containers shall
be
(a) separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h,
(b) designed for the storage of oxygen containers only,
(c) vapour tight,
(d) lined with noncombustible finish,
(e) separately exhausted to the exterior, and
(f) equipped with racks to store the containers.
← Previous3.6.2.8. Emergency Power InstallationsNext →3.6.3.1. Fire Separations for Vertical Service Spaces
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.