3.6.2.5.Storage of Combustible Refuse and Recycling

(1) Except as required by Sentence 3.6.3.3.(9), a room for the temporary storage of combustible refuse and materials for recycling shall be (a) separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h, except that a fire separation with a fire-resistance rating not less than 45 min is permitted where the fire-resistance rating of the floor assembly is not required to exceed 45 min, and (b) sprinklered. (See Note A-3.6.2.5.(1))

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.