3.4.7.4.Protection of Fire Escapes
(1) If a fire escape serves any storey above the second, openings located in a zone described in Sentence (2), including
access doorways in the exterior walls of the building to which the fire escape is attached, shall be protected by closures
conforming to Subsection 3.1.8.
(2) The zone referred to in Sentence (1) extends from any balcony, platform or stairway of a fire escape to a distance
(a) 3 m horizontally,
(b) 10 m below, and
(c) 1.8 m above.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.