3.2.8.5.Protected Floor Space

(1) A protected floor space used to satisfy the requirements of Clause 3.4.3.2.(6)(b) shall (a) be separated from the interconnected floor space by a fire separation having a fire-resistance rating not less than that required for the floor assembly of the storey in which it is located, (b) have all openings in the vertical fire separation between a protected floor space and the adjacent interconnected floor space protected by vestibules conforming to Sentence 3.2.8.4.(1), and (c) be designed so that it is not necessary to enter the interconnected floor space to reach an exit.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.