3.2.8.4.Vestibules
(1) An exit opening into an interconnected floor space shall be protected at each opening into the interconnected floor
space by a vestibule
(a) with doorways that are not less than 1.8 m apart,
(b) that is separated from the remainder of the floor area by a fire separation that is not required to have a fire-
resistance rating, and (See Note A-3.1.8.1.(1)(b))
(c) that is designed to limit the passage of smoke so that the exit stair shaft does not contain more than 1% by volume of
contaminated air from the fire floor, assuming an outdoor temperature equal to the January design temperature on a
2.5% basis determined in accordance with MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(See Note A-3.2.8.4.(1)(c))
(2) An exit opening into an interconnected floor space shall conform to Sentence 3.4.3.2.(6).
(3) If an elevator hoistway opens into an interconnected floor space and into storeys above the interconnected floor
space, either the elevator doors opening into the interconnected floor space or the elevator doors opening into the storeys
above the interconnected floor space shall be protected by vestibules conforming to Sentence (1).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.