3.2.4.21.Residential Fire Warning Systems
(1) Except where a fire alarm system is installed or required in a building, smoke detectors forming part of a residential
fire warning system installed in conformance with CAN/ULC-S540, “Standard for Residential Fire and Life Safety
Warning Systems: Installation, Inspection, Testing and Maintenance,” are permitted to be installed in lieu of all smoke
alarms required by Article 3.2.4.20., provided that the system is
(a) capable of sounding audible signals in accordance with Sentences 3.2.4.20.(12) and (16),
(b) provided with a visual signalling component in accordance with Sentences 3.2.4.22.(17) to (19),
(c) powered in accordance with Sentence 3.2.4.20.(9), and
(d) provided with a silencing device in accordance with Sentences 3.2.4.20.(14) and (15).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.