PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.4.15.System Monitoring
(1) An automatic sprinkler system shall be equipped with waterflow detecting devices and, if an annunciator is required
by Article 3.2.4.8., shall be installed so that each device serves
(a) not more than one storey, and
(b) an area on each storey that is not more than the system area limits as specified in NFPA 13, “Standard for the
Installation of Sprinkler Systems.”
(2) Waterflow detecting devices required by Sentence (1) shall be connected to the fire alarm system so that, upon its
actuation, an alert signal or an alarm signal is initiated.
(3) The actuation of each waterflow detecting device required by Sentence (1) shall be indicated separately on the fire
alarm system annunciator.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.