PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.4.14.Elevator Emergency Return
(1) Except as permitted by Sentence (3), in a building having elevators that serve storeys above the first storey and that
are equipped with an automatic emergency recall feature, smoke detectors shall be installed in the elevator lobbies on the
recall level so that when these smoke detectors are actuated, the elevators will automatically return directly to an alternate
floor level.
(2) Smoke detectors required by Sentence (1) shall be designed as part of the building fire alarm system.
(3) The alternate floor recall feature required by Sentence (1) is not required if the floor area containing the recall level
is sprinklered throughout.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.