PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.3.9.Protection of Structural Members
r1 (1) Structural members, including beams, columns and arches, placed wholly or partly outside the exterior face of a
building and are less than 3 m from the property line or the centre line of a public thoroughfare shall be protected from
exterior fire exposure by fire protection having a fire-resistance rating not less than that required for their protection from
interior fire exposure, as stated in Articles 3.2.2.20. to 3.2.2.93., but not less than 1 h.
(2) Structural members of heavy timber construction, including beams, columns and arches, that are placed wholly or
partly outside an exterior face of a building and are 3 m or more from the property line or the centre line of a public
thoroughfare need not be covered with noncombustible cladding.
← Previous3.2.3.8. Protection of Exterior Building FaceNext →3.2.3.10. Unlimited Unprotected Openings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.