PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.3.10.Unlimited Unprotected Openings
(1) An exposing building face in a storage garage with all storeys constructed as open-air storeys is permitted to have
unlimited unprotected openings provided it has a limiting distance not less than 3 m.
(2) The exposing building face of a storey that faces a street and is at the same level as the street is permitted to have
unlimited unprotected openings if the limiting distance is not less than 9 m.
← Previous3.2.3.9. Protection of Structural MembersNext →3.2.3.11. Low Fire Load, One Storey Building
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.