3.13.8.4.Emergency Operation of Elevators

(1) Manual emergency recall operation shall be provided for all elevators. (2) Key-operated switches for emergency recall described in Sentence (1) shall be provided and shall be located on the outside of each elevator shaft at the level of the fare-paid area control. (3) In-car emergency service switches shall be provided in all elevator cars. (4) Keys to operate the switches required in Sentences (2) and (3) shall be located at (a) the annunciator required in Clause 3.13.5.5.(1)(a), and (b) the collector’s booth designated in Clause 3.13.5.5.(1)(b).

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.