3.13.6.2.Washrooms Required
(1) Except as provided in Sentences (2) and (3), a washroom for each sex, containing at least one water closet and one
lavatory, shall be provided in each rapid transit station for use by employees.
(2) Where the number of employees in a rapid transit station is not more than five, a washroom containing one water
closet and one lavatory is permitted to be used by both sexes provided the door to the room can be locked from the inside.
(3) Where a rapid transit station is not staffed during operating hours, a washroom is not required in the station.
(4) In each rapid transit station located at the end of a line, a washroom for each sex, containing no fewer than three
water closets and two lavatories, shall be provided for use by the public.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.