3.13.5.6.Annunciator Indication

(1) All fire alarm, fire detectors, valve switches and water flow indicator signals when activated in a rapid transit station shall be indicated on the annunciator at the station. (2) The annunciator at a rapid transit station shall be monitored simultaneously at the central supervising station. (3) Where a means of egress from a rapid transit station leads through an adjoining building, any alarm signal originating in the building within 2 storeys above a connection to the station shall (a) be indicated on the rapid transit station annunciator, and (b) cause a message to flash a warning on a sign located in conformance with Sentence (4), that the means of egress shall not be used as an exit from the station. (4) A sign required in Clause (3)(b) shall be located (a) at the doors from the rapid transit station to the adjoining building, and (b) in the means of egress to the adjoining building, at the last point where there is a choice of direction to travel to at least one other exit.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.