3.13.5.11.Standpipe and Hose Systems
(1) A standpipe and hose system conforming to the requirements of Articles 3.2.5.8. to 3.2.5.11. be installed in a rapid
transit station, except as otherwise required or permitted in this Article.
(2) Where a rapid transit station includes more than one standpipe riser there shall be a cross-connection pipe having a
diameter not less than 100 mm between each standpipe riser so that supplying of water through any fire department
connection will furnish water throughout each riser.
(3) There shall be identification on a fire department connection for a standpipe system in a rapid transit station to
indicate that the connection is part of the station system.
(4) Hose stations shall be located so that every portion of the rapid transit station can be reached by a hose stream and
is within 3 m of a hose nozzle when the hose is extended.
(5) In addition to the requirements in Sentence (4), hose stations shall be located in each tunnel not more than 20 m
from the end of the platform.
(6) Each hose station shall have a 38 mm hose connection and a 65 mm hose connection.
(7) All supply piping shall have a diameter not less than 100 mm.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.