PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.13.3.2.Booths and Kiosks
(1) Booths and kiosks that are not more than 20 m 2 in area and are used only by the transit agency for fare collection,
dissemination of information or similar non-mercantile occupancies shall be of noncombustible construction and are not
required to be separated from the remainder of the floor area by a fire separation.
(2) Booths and kiosks that are more than 20 m2 in area and are used only by the transit agency for fare collection,
dissemination of information or similar non-mercantile occupancies shall be
(a) sprinklered, and
(b) separated from the remainder of the floor area by a fire separation of noncombustible construction that is not
required to have a fire-resistance rating.
(3) A door acting as a closure in the fire separation in Sentence (2) is not required to be equipped with a self-closing
device.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.