3.1.9.4.Combustible Piping Penetrations
(1) Combustible sprinkler piping is permitted to penetrate a fire separation provided the fire compartments on each side
of the fire separation are sprinklered.
(2) Combustible water distribution piping is permitted to penetrate a fire separation that is required to have a fire-
resistance rating, provided the piping is protected at the penetration with a firestop in conformance with Clause (4)(a) or
(b).
(3) Except as permitted by Sentences (4), (5), (7) and (8), combustible piping shall not be used in a drain, waste and
vent piping system if any part of that system penetrates
(a) a fire separation required to have a fire-resistance rating, or
(b) a membrane that forms part of an assembly required to have a fire-resistance rating.
(4) Combustible drain, waste and vent piping is permitted to penetrate a fire separation required to have a fire-
resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating, provided
(a) except as provided in Clause (b), the piping is sealed at the penetration by a firestop that has an F rating not less than
the fire-resistance rating required for the fire separation when subjected to the fire test method in CAN/ULC-S115,
“Standard Method of Fire Tests of Firestop Systems,”
(b) in buildings more than 3 storeys in building height, the piping is sealed at the penetration by a firestop that has an F
rating not less than the fire-resistance rating required for the fire separation when subjected to the fire test method in
CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” with a pressure differential of 50 Pa
between the exposed and unexposed sides, with the higher pressure on the exposed side, and
(c) the piping is not located in a vertical service space.
(5) Combustible drain, waste and vent piping is permitted on one side of a vertical fire separation provided it is not
located in a vertical service space.
(6) Combustible piping for central vacuum systems is permitted to penetrate a fire separation, provided the installation
conforms to the requirements that apply to combustible drain, waste and vent piping specified in Sentence (4).
(7) Except as provided in Sentence (8), penetrations of a fire separation that incorporate transitions between
combustible and noncombustible drain, waste and vent piping shall be sealed by a firestop that has an F rating not less
than the fire-resistance rating required for the fire separation when subjected to the fire test method in CAN/ULC-S115,
“Standard Method of Fire Tests of Firestop Systems,” with a pressure differential of 50 Pa between the exposed and
unexposed sides, with the higher pressure on the exposed side.
(8) Transitions between vertical noncombustible drain, waste and vent piping and combustible branches for drain, waste
and vent piping are permitted on either side of a fire separation, provided they are not located in a vertical service space.
(See Note A-3.1.9.4.(8))
(9) Combustible piping not more than 25 mm in diameter containing chlorine gas is permitted to penetrate a fire
separation between a chlorine gas service room built in conjunction with a public pool or public spa and the remainder of
the building, provided the piping is sealed at the penetration by a firestop in conformance with Clause 3.1.9.1.(1)(a).
← Previous3.1.9.3. Penetration by Outlet Boxes (See Note A-3.1.9.3.Next →3.1.9.5. Openings Through a Membrane Ceiling
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.