3.1.5.25.Wires in Computer Room Floors
(1) Optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes, located in the
space below a raised floor in a computer room, are permitted in a building required to be of noncombustible construction
provided they do not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical
Flame Test in Clause 4.11.1. of CSA C22.2 No. 0.3, “Test methods for electrical wires and cables,” (FT1 Rating).
(2) The requirement in Sentence (1) is considered to be met where the wires and cables
(a) exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in
Cabletrough in Clause 4.11.4. of CSA C22.2 No. 0.3, “Test methods for electrical wires and cables,” (FT4 Rating),
or
(b) exhibit a flame-spread of not more than 1.5 m, a smoke density of not more than 0.5 at peak optical density and a
smoke density not more than 0.15 at average optical density when tested in conformance with the Flame and Smoke
Test in the Appendix to CSA C22.2 No. 0.3, “Test methods for electrical wires and cables,” (FT6 Rating).
← Previous3.1.5.24. Wood Decorative CladdingNext →3.1.5.26. Combustible Components in Public Pools and Publi
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.